Technical Specifications
Power System
Power supplied from two separate sub-stations
3.2MVA Diverse 11kV supply (2N)
Diesel Backup Generators (N+1)
Diesel is delivered every 4 hours to allow continuous operation
UPS system (N+1)
Up to 136A per rack (30kW)
Dual power feed to each rack (2N)
100% renewable energy sources
No CO2 emissions
Cooling System
We use natural free cooling
Air-to-Air heat exchangers
Closed Loop air system in each POD and building
Cooling is managed in 1/2 rack modules (top and bottom)
No water is used for any part of the cooling system
Security
ISO27001 Certified
4 Zone Security System
24/7/365 Monitoring
Unified SCADA system
Fire Suppression
Zoned Fire Suppression
VESDA Smoke detection
Argon Gas fire suppression system
No water is used in the fire suppression system
Connectivity
Diverse multi-terabit connectivity
Internet connectivity with peering options in the United Kingdom, North America and Denmark.
MPLS POP in the United Kingdom